Features
-
Serial
I/O Module
-
Analog Input Channels: 4
-
Input
Type: Pt, Ni
-
Sampling
rate: 10 samples/sec
-
Bandwidth:
4 Hz
-
Wire
connection: 2/3/4
-
Accuracy:
+/- 0.05% or better
-
Zero
drift: +/-0.3µV/ ¢J
-
CMR
@ 50/60 Hz: 92 dB min.
-
NMR
@ 50/60 Hz: 100 dB
-
Span
drift: +/- 25 ppm/¢J
-
Power
Consumption:3W
RTD
temperature range
|
Pt100
|
-100¢J
|
to
|
+100¢J
|
£\=0.00385
|
|
Pt100
|
0¢J
|
to
|
+100¢J
|
£\=0.00385
|
|
Pt100
|
0¢J
|
to
|
+200¢J
|
£\=0.00385
|
|
Pt100
|
0¢J
|
to
|
+600¢J
|
£\=0.00385
|
|
Pt100
|
-100¢J
|
to
|
+100¢J
|
£\=0.003916
|
|
Pt100
|
0¢J
|
to
|
+100¢J
|
£\=0.003916
|
|
Pt100
|
0¢J
|
to
|
+200¢J
|
£\=0.003916
|
|
Pt100
|
0¢J
|
to
|
+600¢J
|
£\=0.003916
|
|
Ni120
|
-80¢J
|
to
|
+100¢J
|
|
|
Ni120
|
0¢J
|
to
|
+100¢J
|
|
|
|