Communication
The I-8437 / 8837 provides
ethernet solutions. It contains 4 communication ports, COM1:RS232,
COM2: 10M ethernet , COM3:RS232/RS485, COM4:RS232.
The I-8417 / 8817 provides
RS485 solutions. It contains 4 communication ports, COM1:RS232,
COM2: RS485, COM3: RS232 / RS485, COM4:RS232.
These different
communication ports can provide different kinds of usage include
RS485 networking, controller to controller data-exchange, Modbus /
Modbus TCP protocol, remote I/O extension, linking with HMI / MMI,
program download / upload , and debugging.
Modbus
& Modbus TCP/IP
Modbus is a widely used
communication protocol. The I-8417 / 8817 supports Modbus RTU
protocol on RS232 (COM1) and RS485 (COM2). The I-8437 / 8837
supports Modbus RTU protocol on RS232 (COM1) and Modbus TCP/IP
protocol on Ethernet (COM2).
Any HMI (for example,
Iconics, Intouch, FIX, Citect, Wizcon, Labview, Lablink, ...),
Modbus OPC server, touch monitors (for example, The Touch 506, Touch
509, Touch 510) or other MMI devices can easily talk with the I-8xx7
by Modbus protocol. It is easy to find software and devices with the
Modbus protocol on the market. Or, by using VB, VC programming,
users can design software with Modbus protocol to talk with the
controller.

Modbus
Master
The COM1 and COM2 of
I-8417/ 8817/ 8437/ 8837 are Modbus slave ports. PC and HMI are the
Modbus master and talk with the Modbus slave port of COM1 or COM2 of
the controllers. Moreover, I-8xx7 can also provide Modbus Master
protocol on either COM3 or COM4 of the controllers, in order to
talk to devices with Modbus slave protocol, such as PLC, RTU, power
meter¡K

Multi-client Connection
Each I-8437 / 8837 has an
Ethernet port and can take your control system to Internet world.
Each I-8437 / 8837 has an IP address and with a fixed Ethernet port
No. of 502. Up to 5 PCs can link to one I-8437 / 8837 through
Ethernet. Another PC or MMI can link to COM1: RS232 port of the
I-8437/ 8837. Therefore, the maximum number of clients that can be
linked is 6.
For the I-8417/ 8817, the
maximum number of clients that can be linked is 2, one linking to
COM1: RS232 and the other linking to COM2: RS485.

RS485 Network
One PC or HMI can link to
one I-7520 converter to talk to a maximun of 255 I-8417 / 8817
controllers on a RS485 network. The I-8417 / 8817 uses COM2:RS485 as
its RS485 network port. Each controller on the same RS485 network
should set its unique NET-ID to make networking smooth and
error-free. The max. distance can be up to 1200 meters with the
terminal resistors.
Data Exchange via Fbus or
Ebus
Fbus ( RS-485 network )
Each I-8xx7 can use its
other RS-485 port ( COM3 ) to talk to each other via the Fbus
communication mechanism . Fbus can be used to broadcast data to each
controller or each controller can request to send or receive data
from any other controller on the same Fbus network.
Ebus ( Ethernet network)
Each 8437 / 8837 can use
its ethernet port ( COM2 ) to talk to each other via the Ebus
communication mechanism. When the PC is talking with controllers via
ethernet, the controllers can also talk to eachother via the same
Ethernet, It makes the configuration more flexible and faster.

Sening Email
The ISaGRAF driver inside
the I-8417 / 8817 / 8437 / 8837 provides ¡§Email¡¨ function block to
send email form the COM4 of the controller via a general modem. Then
it will be an useful and easy way to send an alarm message to the
system operator. Or it can becom a production report system.
Various IO boards / Remote
IO Extension
The I-8417 / 8437 provides
4 empty slots while the I-8817 / 8837 provides 8 empty slots
on-board. The IO boards include Digital I/O, Relay output, SSR-DC/AC
output, AC input, Strain Gauge input, Analog I/O, RTD, Thermocouple,
counter, frequency, and more. There are more than 30 different I/O
boards available now and, in the future, there will be more. The
max. channel provided by the I-8040 / 8041 / 8042 Digital I/O
boards is 32.
|
Remote IO modules are
useful for some distributed applications. The I-8417 / 8817 / 8437 /
8837 can integrate with the I-7000 and I-87xx modules by linking one
of its COM3 or COM4 ports to each remote I/O module. A max. number
of 64 remote I/O modules can be linked to one controller and max.
number of 16 I/O channels for some remote I/O modules.
Remotely Download Program:
Modem_Link
The Mode_Link is an
software designed by ICP DAS, which need to be installed into the
ISaGRAF software in your PC. The Modem_Link provide you a easy way
to remotely download your ISaGRAF program to the I-8417/ 8817/ 8437/
8837 via a general modem. And also you can monitor every I/O, data
and if the program allows, you can controll it via the Modem.
MMICON:
ICP DAS's Man Machine Interface
The
I-8417/8817/8437/8837 & I-7188EG/XG support the ICP DAS's MMICON
to become their Man Machine Interface. The MMICON is featured with a
240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display
picture, string, integer, float, and input a character, string,
integer and float. All control logic is written in ISaGRAF program.
How to use ?
ftp://ftp.icpdas.com/pub/cd/8000cd/napdos/isagraf/8000/
english_manu/c16.pdf
Data log :
data, date & time can be
stored at S256/S512, and then PC can load these data via
RS232/RS485, ethernet & Modem.
Features & Specifications
-
General environment
Operating temperature:
-25¢XC to +75¢XC
Storage temperature:
-40¢XC to +85¢XC
Humidity: 0 to 95 %
(non-condensed)
Built-in Watch Dog Timer
Built-in power
protection & network
protection circuit
-
System
CPU: 80188-40 or
compatiable
SRAM: 512K bytes
FLASH ROM: 512K bytes
COM4 support full modem
signals.
COM ports for the I-8417
& 8817:
COM1:RS-232, COM2:RS-485,
COM3:RS232/RS485,
COM4:RS232
COM ports for the I-8437
& 8837:
Ethernet: 10 BaseT
COM1:RS-232,
COM3:RS232/RS485, COM4=RS232
Program download from PC
to COM1, COM2 & Ethernet
Built-in 64-bits
hardware unique serial number
4 empty I/O slots for
I-8417 & 8437 for
I-8000 parallel & serial I/O boards.
8 empty I/O slots for
I-8817 & 8837 for
I-8000 parallel & serial I/O boards
SMMI: Built-in five
7-Seg. Leds, four
pushbuttons, & three Leds on the front
panel
for using as Simple Man
Machine Interface.
-
Software
Supports IEC61131-3:
ISaGRAF
Programming languages:
LD, FBD, SFC, ST, IL & FC
Real Time Clock
Year-2000 compliance
Gives seconds, minutes,
hours, date of the month, month and year, from 1980 to 2079
-
NVSRAM
31 bytes, battery
backup, data valid up to 10 years
-
EEPROM
2048 bytes (8 blocks,
each 256 bytes)
Data retention > 100
years. 1,000,000 erase/write cycles
l Flash Memory
512K bytes, Erase unit
is one sector (64K bytes)
100,000 erase/write
cycles
-
COM1
RS-232:
TXD,RXD,RTS,CTS,GND
Communication speed:
115200 max.
Supports Modbus Serial
Protocol for Connecting PC/HMI & Touch panels
-
COM2
for I-8417 & 8817
RS-485: Data+, Data-,
self-tuner ASIC inside
Communication speed:
115200 max.
Supports Modbus Serial
Protocol for Connecting PC/HMI & Touch panels
-
Ethernet for I-8437 & 8837
10 BaseT Connector, 10M
bps, NE2000 compatible
Supports Modbus TCP/IP
Protocol for Connecting PC/HMI & Touch panels
-
COM3
RS232/RS485: 115200 bps
max.
RS232:
TXD,RXD,RTS,CTS,GND
RS485: Data+, Data-
Supports Protocol of
I-7000 & I-87K Remote I/O Modules
Supports Modbus Master
Protocol for connecting other Modbus devices
Supports User self
defined Protocol
-
COM4
RS232: 115200 bps max.
Full modem signals: TXD,
RXD, RTS, CTS, DSR, DTR, DCD, RI, GND
Supports Protocol of
I-7000 & I-87K Remote I/O Modules
Supports Modbus Master
Protocol for connecting other Modbus devices
Supports User self
defined Protocol
-
Modem_Link
Supports PC Remotely
download the program to faraway controllers through a general
Modem.
-
Controller to Controller Data Exchange
Supports ¡§Ebus¡¨ software
mechanism built in the ethernet port of the I-8437 & 8837 to
exchange data with each other.
Supports ¡§Fbus¡¨ software
mechanism built in the COM3:RS485 port of the I-8417, 8817, 8437
& 8837 to exchange data with each other.
-
Sending Emails
COM4 supports the
software protocol to
send eamils via one
general modem.
-
Power
Power requirements: 10
to 30V DC (unregulated)
Power consumption: 20W
Options:
-
DIN-540A: 24VDC, 1.7 Amps.
DIN-Rail Mounting Power supply
-
I-workbench-80: ISaGRAF
workbench, supports 80 I/O tags
-
I-workbench-256: ISaGRAF
workbench, supports 256 I/O tags
-
S-256: 256 KBytes Battery
Backup RAM
-
S-512: 512 KBytes Battery
Backup RAM
|