The
I-7188EG is an embedded controller and powered by an
80188-40 processor with 512K bytes of static RAM, and 512K bytes of
Flash memory. It provides one serial RS-232 port, one RS-485 port
and one 10BASE-T port. Each
I-7188EG has an
Ethernet port and can take your system to the internet world. The I-7188EG
also supports an optional battery back-up SRAM expansion board and
Flash-Rom board, providing non-volatile mass storage from 2
megabytes to 64 megabytes.
Creating a modbus Link with the I-7188EG
The
I-7188EG controller can be a Modbus "Slave" and/or a Modbus "Master"
controller depending on the application. As a Modbus slave, you can
use COM1 (RS232) and the Ethernet port of the I-7188EG controller to
link to PCs or other HMI products. As a Modbus master, you can use
COM2 (RS485) to talk to other PLCs or devices which support Modbus
protocol.

Linking the I-7000 & I-87xx modules for remote I/O
The
I-7188EG controller can use its COM2 (RS485) port to link to ICP
DAS's "I-7000" & ¡§I-87xx¡¨ series ( Note1) of remote I/O modules.
This configuration can be very useful in applications that require
distributed remote I/O throughout the system.
I/O Expansion Boards
The
I-7188EG has an I/O expansion bus which can plug an expansion I/O
board. Available I/O boards are as X107, X202, X203, X303, X304,
X305, X503, X504, X505, X506, X507, X508, X509, X510 and more.
Linking To An MMI Interface Device
The
COM1 (RS-232) port of the I-7188EG controller can be used to
interface with additional Man Machine Interface (MMI) devices such
as touch screen displays. ICP DAS provides a full line of touch
screen displays, such as the "Touch" series screens. The models in
the product line include the Touch 506, Touch 509 and the Touch 510
MMI products.

Controller to Controller Data Exchange
Like
the I-8437 / 8837 controllers, the I-7188EG can use its Ethernet
port to talk to one aother via the Ebus (Ethernet network) software
communication mechanism.

Multi-client Connection
Each
I-7188EG has an IP address and with a fixed port No. of 502.
With
Modbus TCP/IP protocol, up to 5 PCs can link to one I-7188EG
through Ethernet. With Modbus serial protocol, another PC or MMI can
link to the COM1 (RS232) port of the I-7188EG. Therefore, the
maximum number of clients that can be linked is 6.
|

MMICON:
ICP DAS's Man Machine Interface
The
I-8417/8817/8437/8837 & I-7188EG/XG support the ICP DAS's MMICON
to become their Man Machine Interface. The MMICON is featured with a
240 x 64 dot LCD and a 4 x 4 Keyboard. User can use it to display
picture, string, integer, float, and input a character, string,
integer and float. All control logic is written in ISaGRAF program.
How to use ?
ftp://ftp.icpdas.com/pub/cd/8000cd/napdos/isagraf/8000/
english_manu/c16.pdf
Data log :
data, date & time can be
stored at X607 /
X608, and then PC can load these data via RS232 & ethernet.
Features & Specifications
-
CPU: 80188-40
-
10BASE-T NE2000 compatible Ethernet
Controller
-
Reloadable Operating Software
-
Remote Configuration, Diagnostics
-
64-bit hardware unique serial number
inside
-
COM
driver
support
interrupt & 1K QUEUE input buffer
-
COM port: COM1, COM2,
-
Built-in RTC, NVRAM, EEPROM
-
User defined 14 I/O lines
-
Built-in I/O expansion bus interface
-
Built-in MiniOS7
-
-
Program download port: COM1
-
SRAM:
512 bytes
-
Flash
Memory:
512 K bytes
-
NVSRAM:
31 bytes
-
EEPROM:
2048 bytes
-
Real Time Clock
-
COM1:
RS-232: TXD, RXD, RTS, CTS, GND
-
COM2:
RS-485: D1+, D1-, self-tuner ASIC inside
-
Power
requirements: 10 to 30VDC(non-regulated)
-
Power consumption:
2.0W for I-7188EG; 3.0W for
I-7188EGD
-
Dimensions:
123 x mm x 72 mm x 33 mm
-
-
-
DIN-KA52F
: 1.05 Amp. DIN-Rail Mounting
Power supply
-
ISaGRAF-80
: ISaGRAF workbench, supports 80 I/O tags
-
ISaGRAF-256
: ISaGRAF workbench, supports 256 I/O tags
-
X600
: 4 Mega Bytes NAND Flash memory
expansion Board
-
X601: 8 Mega Bytes NAND Flash
memory expansion Board
-
X607
: 128K bytes SRAM expansion board
-
X608
: 512K bytes SRAM
expansion board
|